Page 436 - 2015 Master Catalog
P. 436

DR-30-24

30W/1.5A 24VDC DIN-Rail Industrial Power Supply

                                                                Features

                                                                •	 -20°C to 60°C operating temperature range
                                                                •	 Can be installed on DIN-rail TS-35 / 7.5 or 15
                                                                •	 Protections: Short circuit / Over load / Over voltage
                                                                •	 UL60950-1, TUV EN60950-1 approved
                                                                •	 Universal AC input / Full range

Hardware Specifications                                               Over Load Protection
                                                                       •	105 to 160% rated output power
Power                                                                  •	Protection type : Constant current limiting, recovers

      Power Input                                                        automatically after fault condition is removed
       •	Voltage Range: 85 to 264VAC, or 120 to 370VDC
       •	Frequency Range: 47 to 63Hz                            Environment
       •	Efficiency: 83%
       •	AC Current (Typ.): 0.88A / 115VAC; 0.48A / 230VAC            Operating Temperature
       •	Inrush Current (Typ.): Cold Start 15A / 115VAC; 30A /         •	-20°C to 60°C (Refer to output load derating curve)
                                                                      Storage Temperature
         230VAC                                                        •	-40°C to 85°C (-4°F to 158°F)
      Power Output                                                    Working Humidity
       •	DC Voltage: 24V                                               •	20% to 90%RH non-condensing
       •	Rated Current: 1.5A                                          Storage Humidity
       •	Current Range: 0 to 1.5A                                      •	10% to 95%RH
       •	Rated Power: 36W                                       Regulatory Approvals
       •	Ripple & Noise (max.): 150mVp-p
       •	Voltage Adj. Range: 21.6 to 26.4V                            Safety
       •	Voltage Tolerance: + / - 1.0%                                 •	UL60950-1, TUV EN60950-1, design refer to EN50178
       •	Line Regulation: + / - 1.0%                                  EMC
       •	Load Regulation: + / - 1.0%                                   •	EN55011
       •	Setup, Rise Time: 100ms, 30ms / 230VAC;                       •	EN55022 (CISPR22) Class B
                                                                       •	EN61000-3-2, -3
                               100ms, 30ms / 115VAC                    •	Withstand Voltage
                               at full load
       •	100ms, 30ms / 115VAC at full load                                ◦◦ I/P-O/P: 3KVAC
       •	Hold up Time: 100ms / 230VAC; 100ms, 21ms / 115VAC at         •	Isolation Resistance
         full load
                                                                          ◦◦ I/P-O/P: 100M Ohms / 500VDC
Mechanical                                                          EMS

      Casing                                                          EN61000-4-2,3,4,5,6,8,11
       •	Plastic case                                                 ENV50204
      Dimensions                                                      EN55024
       •	78mm (W) x 56mm (D) x 93 mm(H)                               EN61000-6-2
                                                                      EN61204-3 Heavy industry level, criteria A
         (3.12" (W) x 2.24" (D) x 3.72" (H))                        Environmental Test Compliance
      Weight                                                           •	Vibration
       •	0.27kg (0.59 lb)
      Installation                                                        ◦◦ 10 to 500Hz, 2G 10min. / 1 cycle, period
       •	DIN-Rail                                                           for 60 min. each along X, Y, Z axes
    Protection
      Over Voltage Protection
       •	27.6 to 32.4V
       •	Protection type : Shut down o/p voltage,

         re-power on to recover

DR-30-24                                                        24 www.EtherWAN.com

                                                                                                                                                     rev. A1.2
   431   432   433   434   435   436   437   438   439   440   441