Page 438 - 2015 Master Catalog
P. 438

DR-30-12

24W/1.5A DIN-Rail 24VDC Industrial Power Supply

                                                                   Features

                                                                   •	 -20°C to 60°C operating temperature range
                                                                   •	 Can be installed on DIN-rail TS-35 / 7.5 or 15
                                                                   •	 Protections: Short circuit / Over load / Over voltage
                                                                   •	 Isolation class II
                                                                   •	 UL60950-1, TUV EN60950-1 approved

Hardware Specifications                                                  Over Load Protection
                                                                          •	105 to 160% rated output power
Power                                                                     •	Protection type : Constant current limiting, recovers

      Power Input                                                           automatically after fault condition is removed
       •	Voltage Range: 85 to 264VAC; 120 to 370VDC
       •	Frequency Range: 47 to 63Hz                               Environment
       •	Efficiency: 81%
       •	AC Current (Typ.): 0.88A / 115VAC; 0.48A / 230VAC               Operating Temperature
       •	Inrush Current (Typ.): Cold Start 15A / 115VAC;                  •	-20°C to 60°C (Refer to output load derating curve)
                                                                         Storage Temperature
         30A / 230VAC                                                     •	-40°C to 85°C (-4°F to 158°F)
      Power Output                                                       Working Humidity
       •	DC Voltage: 12V                                                  •	20% to 90%RH non-condensing
       •	Rated Current: 2A                                               Storage Humidity
       •	Current Range: 0 to 2A                                           •	10% to 95%RH
       •	Rated Power: 24W                                          Regulatory Approvals
       •	Ripple & Noise (max.): 120mVp-p
       •	Voltage Adj. Range: 10.8 to 13.2V                             Safety
       •	Voltage Tolerance: + / - 1.0%
       •	Line Regulation: + / - 1.0%                                     UL EN60950-1
       •	Load Regulation: + / - 1.0%                                     TUV EN60950-1, design refer to EN50178
       •	Setup, Rise Time: 100ms, 30ms / 230VAC;                       EMC

                               100ms, 30ms / 115VAC                      EN55011
                               at full load                              EN55022 (CISPR22) Class B
       •	Hold up Time: 100ms / 230VAC; 21ms / 115VAC at full load        EN61000-3-2, -3
                                                                          •	Withstand Voltage:
Mechanical
                                                                             ◦◦ I/P-O/P: 3KVAC
      Casing                                                              •	Isolation Resistance:
       •	Plastic case
      Dimensions                                                             ◦◦ I/P-O/P: 100M Ohms / 500VDC
       •	78mm (W) x 56mm (D) x 93 mm(H)                                EMS

         (3.12" (W) x 2.24" (D) x 3.72" (H))                             EN61000-4-2,3,4,5,6,8,11
      Weight                                                             ENV50204
       •	0.27kg (0.59 lb)                                                EN55024
      Installation                                                       EN61000-6-2
       •	DIN-Rail                                                        EN61204-3 Heavy industry level, criteria A
    Protection                                                         Environmental Test Compliance
      Over Voltage Protection                                             •	Vibration
       •	13.8 to 16.2V
       •	Protection type: Shut down o/p voltage, re-power on to              ◦◦ 10 to 500Hz, 2G 10min. / 1 cycle, period
                                                                               for 60 min. each along X, Y, Z axes
         recover

DR-30-12                                                           26 www.EtherWAN.com

                                                                                                                                                        rev. A1.2
   433   434   435   436   437   438   439   440   441   442   443